Award

Portfolio Data

Icon: back arrowBack to Award Search

Ground Fault Detection System

Awardee

HEPBURN AND SONS LLC

9200 CHURCH ST STE 302
MANASSAS, VA, 20110-5561
USA

Award Year: 2025

UEI: TLLAP6FKHA99

HUBZone Owned: No

Woman Owned: No

Socially and Economically Disadvantaged: No

Congressional District: 10

Tagged as:

STTR

Phase II

Seal of the Agency: DOD

Awarding Agency

DOW

Branch: NAVY

Total Award Amount: $1,699,926

Contract Number: N68335-23-C-0217

Agency Tracking Number: N21A-T005-0079

Solicitation Topic Code: N21A-T005

Solicitation Number: 21.A

Abstract

Hepburn and Sons LLC proposes a ground fault detection system design for 440VAC three phase radial Navy shipboard power distribution, while teaming with their partner Florida State University, Center for Advanced Power Systems (FSU CAPS). Existing Navy ground fault detection systems can detect and locate single line to ground faults on a given phase, but a second ground fault on a separate phase causes a line-to-line fault which trips breakers and removes power from downstream loads. Quickly detecting, locating, and resolving an initial single ground fault can mitigate the risk of double faults and loss of power to mission critical equipment. The ground fault detection and localization system design will function for both permanent and non-permanent fault cases, particularly for USN Shipboard 440VAC three phase radial power distribution either grounded or ungrounded. The low voltage alternating current interface standard, MIL-STD-1399-300-1, provides further characteristics. For ungrounded and high resistance grounded power systems, a single line to ground fault is permissible on one of the three phases enabling continued operation. Without the benefit of simplified fault localization of a solidly grounded power system which trips upon a single ground fault, it is critical to quickly identify the faulted piece of Navy equipment or at least identify the shipboard compartment containing the fault. The Hepburn and CAPS team proposes a noise pattern analysis approach to ground fault protection which utilizes machine learning techniques and yields the benefit of passive localization. This approach mitigates an interference issue that comes with conventional protection strategies involving disruptive signal injection as well as manual disconnect hunting of fault localization by trial and error. The methodology is based upon a patent presenting an autonomous fault location approach differentiating fault location by signal oscillatory characteristics (US Patent 8067942 B2, “Method for locating phase to ground faults in DC distribution systems”). In the presence of power electronic switching devices (converter, etc.), this noise pattern analysis-based fault localization does not necessarily require signal injection, but passively monitors a naturally occurring ringing circuit which is altered by a given fault case location. In the absence of such sources of continually occurring switching transients, separate injection of a small amount of signal noise may be required. The team is building upon extensive previous work and intellectual property. The Phase I design approach has been validated for the LVAC radial system of this topic. Phase II will involve prototyping, validating, and demonstrating the approach with plans for shipboard application.

Award Schedule

  1. 2021
    Solicitation Year

  2. 2025
    Award Year

  3. March 26, 2025
    Award Start Date

  4. May 13, 2026
    Award End Date

Principal Investigator

Name: Ben Ford
Phone: (703) 401-5198
Email: ben.ford@hepburnandsons.com

Business Contact

Name: Eric Hepburn
Phone: (703) 366-3434
Email: eric.hepburn@hepburnandsons.com

Research Institution

Name: Florida State University
Phone: (850) 645-9341